The installation of Henan fire rolling shutter door is prone to some problems. One problem is the strength of the transmission device of the fire rolling shutter door. The strength of the roller shutter shaft is also an important parameter of the roller shutter door. At present, there are many unqualified products with this strength, The structure of the roller shutter shaft that seriously affects the use of the fire shutter door mainly refers to the depth of the roller shutter shaft and the shaft heads at both ends plugged into the steel pipe and the depth of the structural shaft head plugged into the steel pipe should be about 110 of the shaft length, and there should be two flanges and enough welds. major fire-resisting window The second problem is the depth of the guide rail. If the depth of the guide rail is not enough and the structure and materials are improper, once encountering a fire, the door curtain is easy to detach from the guide rail and cannot play a role in fire prevention. fire-resisting window Price The third problem is the pre rolling of the fire rolling shutter door. The fire rolling shutter door, especially the steel fire rolling shutter door, is relatively heavy, so a circle of pre rolling will be reserved on the reel to reduce the tension of the curtain weight on the screws. Prevent a curtain from cracking.

A brief talk on the problems encountered in the fire acceptance of Henan fire rolling shutter door 1. The curtain plate coating falls off and rusts, and the curtain plate has obvious pressure pits, concave convex, and penetrating holes. major fire-resisting window The rolling shutter is a complete fire protection product. If the shutter has problems, it will directly affect the fire resistance limit index of the rolling shutter. 2. The guide rail is deformed and the curtain board is stuck or falls unevenly. The fireproof rolling shutter door generally moves along the guide rail. If the guide rail is twisted or broken, the rolling shutter door will not be able to move to the specified position, which will not achieve the effect of fire separation. 3. On the roller shutter, the lower limit fails or the limit line is wrongly connected. fire-resisting window Price This often happens on the fire roller shutter of the atrium. Because the fire roller shutter of the atrium is sometimes installed outside the walkway of the upper floor, there is no floor under the roller shutter to close it, and a large gap is leaked, so the fire separation of the upper and lower floors cannot be reached.

Maintenance and cultivation of Henan fire rolling shutter All fire rolling shutters should be checked and tested once a week. The test content includes: fire rolling shutter escape function test. major fire-resisting window After the fire roller shutter is in the linkage state and drops to the bottom, press any manual button on both sides of the fire roller shutter, and the fire roller shutter shall be able to rise to the limit position (or drop to the bottom again after a delay). The lifting, lowering and stopping test of the manual buttons on both sides of the fire shutter. The fire rolling shutter shall be able to operate according to the instructions, and the operation shall be stable without blocking, not to mention uneven running speed of the shutter, stacking of the shutter or derailment. Test of manual emergency device. The manual zipper is used to lift the fire shutter, and the manual quick release device is used to lower the fire shutter. The fire shutter shall be able to run smoothly. Simulate the fire signal for linkage test. It is required that the fire shutter should be able to descend according to the normal procedure, and the contents and parts displayed in the fire control room should be consistent with the actual situation. Check whether the sealing of fire shutter is intact and damaged. The inspection above Henan fire rolling shutter door shall be carefully recorded, and the problems found shall be solved in a timely manner without leaving hidden dangers. Check whether the appearance of the fire shutter is intact and whether the curtain surface is damaged. Henan fire shutter door The door leaf of Henan fire shutter door cannot move: sensor failure is the major cause of the fire shutter door leaf cannot move. When such a situation occurs, be sure to check whether the sensor signal light is normal. If it is not the fault of the sensor, it may be that the wire connector is loose, the belt falls off, the controller is burned, the foreign matter is stuck, the voltage is abnormal, and so on. Pay attention to check and eliminate them one by one. fire-resisting window Price The door leaf of the fire rolling shutter jumps when opening and closing: the reason for this fault is very simple. If the track of the fire rolling shutter is jammed by foreign matters, it is necessary to check the tracks on both sides of the door leaf, remove the foreign matters, and the fault can be solved. The opening and closing speed of the fire shutter door leaf is too slow: customers often hear this situation. It may be that the speed adjustment of the national controller is too slow, or the belt is too loose, resulting in friction between the fire shutter door leaf and the guide rail. When handling, check these two parts. If the speed is too slow, adjust them faster. If the belt is too loose, tighten it in time.

In order to protect life and property in time and effectively in case of fire, the fire door of Henan refuge room adopts double-sided fireproof board according to the fire protection design requirements of high-rise building refuge room, so as to achieve dual internal and external fire prevention treatment. The Class A 1.50h and Class B 1.00h fully meet the fire protection requirements, which can strive for greater rescue opportunities for people in case of fire, Make sure there is enough time for rescue. major fire-resisting window The fire door of the refuge room is rarely noticed, but it is related to everyone's life safety. When a fire occurs, the fire protection of the refuge bay i] can play the role of fire isolation, isolating the highly toxic smoke and high temperature outside the refuge bay. Provide shelter for people in high-rise buildings and provide more opportunities for emergency rescue. For residential buildings with a building height of more than 54m, each household shall have a refuge room, and the door of the room shall be straight with Class B fireproof door, and the fire resistance integrity of the external window shall not be less than 1.00h. In terms of the current hardbound house configuration in China, a refuge room will be provided for high-rise buildings above 54 meters- The fire resistance limit of the fire door of the general refuge room is about 1h according to the fire control requirements, so that people can escape into the relatively safe environment of the refuge room within one hour of the fire. In recent years, with the growing development of high-rise buildings, skyscrapers have sprung up, and fire doors in shelters have gradually been recognized. fire-resisting window Price In order to meet the requirements of high-end buildings for the fire door of refuge room and the surrounding decoration style. Fire doors in shelters are also new. Style panels are more diverse. It is no longer as rigid and dull as the old fire door.