
Henan fire door technical requirements Wooden fire door is a door with certain fire resistance performance, which is made of fire-resistant wood or fire-resistant wood products as door frame, door leaf framework, door leaf panel. If the door leaf is filled with materials, it is filled with fire insulation materials that are non-toxic and harmless to human body, and is equipped with fire hardware accessories. major anti-theft door The overlapping size of door leaf and door frame shall not be less than 12mm; The fit clearance between the door leaf and the hinge side of the door frame shall not be greater than the dimensional tolerance specified in the design drawings; The fit clearance between the door leaf and the locked side of the door frame shall not be greater than the dimensional tolerance specified in the design drawings; The clearance between the door leaf and the upper frame shall not be greater than 3mm; The gap between two or more door leaves shall not be greater than 3mm; The movable clearance between the door leaf and the lower frame or ground shall not be greater than 9mm; The gap between the door leaf and the door frame binding surface: the gap between the door leaf and the binding surface of the door frame on the hinge side, the lock side and the upper frame shall not be greater than 3mm; The plane height difference between the door leaf and the door frame: On the opening surface of the fire door, the plane height difference between the door frame and the door leaf of Tianjin Telescopic Barcode Reader should not be greater than 1mm. Wooden fireproof door refers to the door frame, door leaf framework and door leaf panel made of wood or wood products, and the fire resistance limit of the door reaches the specified value. Some small deviations between wooden fireproof doors cannot be wrong. Maybe it is a small detail problem, which may fail to meet the standard. anti-theft door direct deal The materials used for Henan fire door are compared first. The fire door has a simple structure and is mainly composed of four parts: door closer, door panel materials (including 06 and 08), door frame materials, and fire panels. Grade A fireproof door is generally made of 08 material with good quality. Its normal service life is 5-8 years. The iron material of the door panel is thick. For the fireproof door with the same thickness, the weight of Grade A fireproof door is greater than that of Grade B.

Henan fireproof rolling shutter door maintenance common faults and treatment methods The fireproof rolling shutter door is constantly applied to large supermarkets, shopping malls, underground garages, workshops and other crowded places. It is inevitable that there will be some small problems that need to be solved. I summarize a few points for your reference. 1、 The fire shutter door does not act: first, check the power supply to see if the power supply air switch of the fire shutter door has power. If there is no power, check the power supply. If there is power, the power indicator of the roller shutter control box should be green at this time. major anti-theft door If the indicator light is not on, then we should check whether the transformer in the control box (the resistance of the transformer is 270 ohms) is burned out. If the power indicator flashes green, it indicates that the power supply may be out of phase. If the power supply is not out of phase, it may be that the standby power board of the control box is burned out; It is also possible that both the power board and the standby power board are burned out. 2、 Henan fire shutter door power supply air switch cannot be pushed up: when delivering the gate, the air switch cannot be pushed up, first check whether there is a problem with the standby board, and the resistance of the output line of the standby board is about 300 ohms. In case of open circuit or short circuit, check whether the motor brake is burnt or whether the spare board is burnt. 3、 The operation button does not work properly: you should first press the Stop key, then press the Reset key, and then press the Up and Down keys. 4、 The indicator lights of the power control box or button panel are all on: at this time, first check whether there is a short circuit in the button line or a button may be pressed to death. If the above phenomenon does not exist, it may be that the chip on the power main board is broken, and then replace the chip. anti-theft door direct deal Pay attention to wearing the clothes in reverse (that is, the opening faces the opening).

Why is Henan fire rolling shutter an indispensable facility? Why is fire rolling shutter an indispensable facility. major anti-theft door The types of fire rolling shutter doors in Henan mainly include composite steel fire rolling shutter (fire and smoke prevention), inorganic super grade fire rolling shutter (double track double shutter), steel composite water spray steam fog fire rolling shutter, steel composite lateral fire rolling shutter, steel composite horizontal fire rolling shutter, inorganic super grade folding fire rolling shutter and fire rolling shutter with various doors. The fireproof rolling shutter door, as well as the firewall, functions as a horizontal fireproof partition. It is composed of 13 parts, such as shutter, base plate, guide rail, support, reel, box, control box, door rolling machine, limiter, door header, manual quick release switch device, button switch and safety device, and is generally installed at the position that is not convenient for firewall separation. For example, open elevator halls, escalators, wide business halls of department stores, exhibition halls of exhibition buildings, and parts of buildings with large openings that cannot use fireproof doors and windows. Fire resisting rolling shutter door has been widely used in building engineering to make fire separation. anti-theft door direct deal Henan fireproof rolling shutter door is an indispensable fire prevention facility in modern high-rise buildings. In addition to the function of ordinary door, the fireproof door has the special functions of fire prevention, smoke separation, suppression of fire spread, and protection of personnel evacuation. It is widely used in high-rise buildings, large shopping malls and other crowded places.

Henan fireproof door is generally set in the following parts. (1) Close the evacuation staircase to the walkway; Enclose the elevator hall, the door leading to the front room and the front room leading to the walkway. (2) Inspection doors of vertical pipe shafts such as cable shafts, pipe shafts, smoke exhaust ducts, garbage ducts, etc. Henan fire door (3) divides the fire compartment, controls the fire wall and the door on the fire partition of the building area of the compartment. major anti-theft door When it is difficult to set firewall or fire door in the building, fire rolling shutter door shall be used instead, and water curtain shall be used for protection. (4) Code (such as GB50016-2014 Code for Fire Protection Design of Buildings) or partition door with special requirements for fire and smoke prevention. For example, the partition doors of equipment rooms (cylinder rooms, foam stations, etc.) attached with fixed fire extinguishing devices in high-rise civil buildings, ventilation, air conditioning rooms, etc. should be Class A fireproof doors; The door on the partition wall of the basement room where people often stay or there are many combustibles shall be Class A fireproof door; Due to limited conditions, it is necessary to arrange oil fired and gas-fired boilers, oil immersed power transformers, high voltage capacitors and switches filled with oil, etc. in high-rise buildings. The doors on the partition walls of special rooms should be Class A fireproof doors. anti-theft door direct deal There are also household doors with special requirements that must be fireproof, such as fire control command center, archives room, valuables warehouse, etc., which usually use Class A or Class B fireproof doors. Fire and burglar proof doors are often used as household doors in high-rise and high-grade residential buildings. GB 12955-2008 Requirements for Fire Resistance of Fire Doors Fire doors are an important part of fire fighting equipment and an important part of social fire prevention. Fire doors should be equipped with fire door closers or door closers that allow normally open fire doors to automatically close the door leaves in case of fire (except for special parts, such as pipeline shaft doors, etc.). That is to say, except for some special parts, such as pipeline well doors, which do not need to install door closers, other parts need to install fire door closers.