Henan fire rolling shutter door is generally installed in the place determined by the process. In addition to the firewall, the fire rolling shutter door should be installed in the two fire compartments where there is no firewall. It is generally located at the following parts. (1) Close the evacuation staircase to the walkway; Enclose the elevator hall, the door leading to the front room and the front room leading to the walkway. (2) Divide the fire compartment and control the fire wall and the door on the fire partition in the building area of the compartment. When it is difficult to set firewall or fire door in the building, fire rolling shutter door shall be used instead, and water curtain shall be used for protection. (3) Code (such as GB50045-95 Code for Fire Protection Design of High rise Civil Buildings) or partition door with special requirements for fire and smoke prevention. high quality Steel fireproof window For example, the partition doors of equipment rooms (cylinder rooms, foam stations, etc.) attached with fixed fire extinguishing devices in high-rise civil buildings, ventilation, air conditioning rooms, etc. should be Class A fireproof doors; The door on the partition wall of the basement room where people often stay or there are many combustibles shall be Class A fireproof door; Due to limited conditions, it is necessary to arrange oil fired and gas-fired boilers, oil immersed power transformers, high voltage capacitors and switches filled with oil, etc. in high-rise buildings. The doors on the partition walls of special rooms should be Class A fireproof doors. There are also household doors with special requirements that must be fireproof, such as fire control command center, archives room, valuables warehouse, etc., which usually use Class A or Class B fireproof doors. Steel fireproof window Price The limited area of Henan fire shutter door special grade fire shutter In the use of special grade fire shutter, because it is mainly used in the rapid formation of fire separation areas, and is mostly set in applications with large space, as a visible fire separation device, generally in the production of fire shutter, fire shutter will be painted with a more striking color, It can not only make the fireproof rolling shutter have a better decorative effect after being folded, but also can remind people of the escape route in fire accidents through eye-catching and penetrating colors in the fire compartment, so as to buy time for effective escape.

The main difference between Henan fireproof door and anti-theft door is that the anti-theft door has a good anti prying sealing performance. Generally, the door cannot be opened without a key after closing the door, and the filler in the door panel is not fireproof material. The security door must be marked with "FAM" and refer to the general technical conditions of security door GB17565-2007. Although the fireproof door is also made of steel, the door plate is filled with fireproof materials, and the thickness of the door plate also has different requirements. The steel door is an ordinary steel door. It also has a certain anti-theft function, but its anti prying performance is relatively poor. This type is common in street processing plants. high quality Steel fireproof window Only Shanghai and Chengdu have local standards for fire and burglar proof doors, and those in other places can only be called fire entry doors, that is, fire doors that reach the standard of fire rated A or B, and (filled with fire door cores) Class A and B standards are generally divided by fire resistance time. At the same time, it meets the anti prying requirements in the following aspects: the door frame is 1.5 thick, and the steel plates on the front and back of the door leaf are 0.8 thick. The lock has the anti prying function, that is, the lock body has both an oblique locking tongue and a square locking tongue. It has the function of quick opening. It is a good twist type, but it is not allowed to install a heaven and earth lock. Locks and cat eyes shall be provided with fire detection reports. Class B fire doors can be fitted with door collars, while Class A fire doors are not allowed. Steel fireproof window Price At the time of acceptance, the merchant must provide fire type approval certificate, fire detection report and metal door detection report. Fire detection report of locks and cat's eyes. The door leaf is opened in the direction of rapid evacuation and cannot be opened inward.

Maintenance and cultivation of Henan fire rolling shutter All fire rolling shutters should be checked and tested once a week. The test content includes: fire rolling shutter escape function test. high quality Steel fireproof window After the fire roller shutter is in the linkage state and drops to the bottom, press any manual button on both sides of the fire roller shutter, and the fire roller shutter shall be able to rise to the limit position (or drop to the bottom again after a delay). The lifting, lowering and stopping test of the manual buttons on both sides of the fire shutter. The fire rolling shutter shall be able to operate according to the instructions, and the operation shall be stable without blocking, not to mention uneven running speed of the shutter, stacking of the shutter or derailment. Test of manual emergency device. The manual zipper is used to lift the fire shutter, and the manual quick release device is used to lower the fire shutter. The fire shutter shall be able to run smoothly. Simulate the fire signal for linkage test. It is required that the fire shutter should be able to descend according to the normal procedure, and the contents and parts displayed in the fire control room should be consistent with the actual situation. Check whether the sealing of fire shutter is intact and damaged. The inspection above Henan fire rolling shutter door shall be carefully recorded, and the problems found shall be solved in a timely manner without leaving hidden dangers. Check whether the appearance of the fire shutter is intact and whether the curtain surface is damaged. Henan fire shutter door The door leaf of Henan fire shutter door cannot move: sensor failure is the major cause of the fire shutter door leaf cannot move. When such a situation occurs, be sure to check whether the sensor signal light is normal. If it is not the fault of the sensor, it may be that the wire connector is loose, the belt falls off, the controller is burned, the foreign matter is stuck, the voltage is abnormal, and so on. Pay attention to check and eliminate them one by one. Steel fireproof window Price The door leaf of the fire rolling shutter jumps when opening and closing: the reason for this fault is very simple. If the track of the fire rolling shutter is jammed by foreign matters, it is necessary to check the tracks on both sides of the door leaf, remove the foreign matters, and the fault can be solved. The opening and closing speed of the fire shutter door leaf is too slow: customers often hear this situation. It may be that the speed adjustment of the national controller is too slow, or the belt is too loose, resulting in friction between the fire shutter door leaf and the guide rail. When handling, check these two parts. If the speed is too slow, adjust them faster. If the belt is too loose, tighten it in time.

The type, type, specification, size, opening direction, device position and anti-corrosion solution of Henan fire rolling shutter door shall meet the design requirements. high quality Steel fireproof window The accessories of the roller shutter door are complete, the position is accurate, the device is stable, and the function should meet the use requirements and various performance requirements of Luoyang roller shutter door. The rolling shutter must be firmly installed, and the number, position, embedding method and connection method with the frame of the embedded parts must meet the design requirements. The appearance of the rolling shutter door shall be clean without scratches and bruises. Eight advantages of Henan fireproof rolling shutter door: energy saving: two key technologies realize energy saving. First of all, the door opening design and double door interlock greatly shorten the door opening cycle. For clean rooms, the shortening of the door opening cycle can reduce the indoor air loss and improve the insulation capacity. In addition, there are double rows of encrypted sealing brushes inside the column of the fast door, and the pvc base card design makes installation and replacement convenient. Cost saving: The fast door is equipped with a LCD display, which will prompt when the door fails to operate, and the code or Chinese display will be displayed. This can avoid costly downtime and time-consuming technical maintenance, which greatly saves costs. Complete types: fast doors include explosion-proof fast doors, wind resistant fast doors, zippered fast doors (also called anti-collision automatic reset fast doors). Rich functions: Henan explosion-proof rolling shutter door can be linked with the air shower room, goods elevator, mechanical arm, assembly line, etc. High efficiency: according to the actual situation and requirements of customers on the site, provide a variety of control switches to improve the efficiency of daily operation. There are radar induction door opening, rope pulling door opening, geomagnetic induction door opening, remote control door opening, card swiping door access control door opening and other door opening methods. Safety: The bottom of Henan fast rolling shutter door is air tight and soft, and the door curtain is soft. There are safety photoelectric devices on both sides of the track. When there are people or obstacles under the door body, the door body will not fall, to ensure that people will not be touched by the door body. Steel fireproof window Price After sales guarantee: the control system of the fast door can timely identify the fault of Henan fast rolling shutter door, and then solve the problem in time. Yuou Door&Window Technology has a special after-sales maintenance department, which can respond within 12 hours if there is a fault.

Relevant requirements for fire protection of the door of Henan Refuge Room What kind of products are qualified when the door of Henan Refuge Room passes the fire protection? Here are some examples: 1. Filling materials: the filling materials must meet the requirements of combustion performance A1 specified in GB8624-2006. At the same time, it meets the requirements of smoke toxicity hazard classification ZA2 specified in GB/T20285-2006. 2. Material thickness: door leaf material shall be no less than 0.8mm, door panel material shall be no less than 0.8mm, door frame plate shall be no less than 1.2mm, hinge plate shall be no less than 3.0mm, reinforcement without screw holes shall be no less than 1.2mm, and reinforcement with screw holes shall be no less than 3.00mm. high quality Steel fireproof window The door of Henan refuge room 3. The adhesive shall meet the requirements of smoke toxicity hazard classification ZA2 specified in GB/T20285-2006. 4. Dimensional deviation: the height of the door leaf shall not exceed 2mm, the width of the door leaf shall not exceed 2mm, the thickness of the door leaf shall be between - 1mm and+2mm, the height of the clipping opening in the door frame shall not exceed 3mm, the width of the clipping opening in the door frame shall not exceed 2mm, and the width of the side wall of the door frame shall not exceed 2mm. 5. Geometric tolerance: the length difference between the two diagonals of the door leaf shall be less than or equal to 3mm, The distortion of the door leaf shall be less than or equal to 5mm, the curvature of the door leaf in the width direction shall be less than 2%, the curvature of the door leaf in the height direction shall be less than 2%, and the length difference between the two diagonals of the inner cutting opening shall be less than or equal to 3mm. 6. Fit tolerance: the overlap size between Manshan and the door frame is less than or equal to 12mm, the fit clearance between the door leaf and the door frame at the hinge side shall not be greater than the size tolerance specified in the design drawing, and the fit clearance between the door leaf and the door frame at the lock side shall not be greater than the size tolerance specified in the design drawing. Steel fireproof window Price The clearance between the door leaf and the upper frame shall be less than or equal to 3mm, the clearance between the double leaf and multi leaf door leaves shall be less than or equal to 3mm, the clearance between the door leaf and the lower frame or the ground shall be less than or equal to 9mm, the clearance between the binding surface of the door leaf and the side of the door frame with hinges shall be less than or equal to 3mm, the clearance between the binding surface of the door leaf and the side of the door frame with locks shall be less than or equal to 3mm, and the clearance between the binding surface of the door leaf and the upper frame of the door frame shall be less than or equal to 3mm, The plane height difference between the door frame and the door leaf is less than or equal to 1mm.

A brief talk on the problems encountered in the fire acceptance of Henan fire rolling shutter door 1. The curtain plate coating falls off and rusts, and the curtain plate has obvious pressure pits, concave convex, and penetrating holes. high quality Steel fireproof window The rolling shutter is a complete fire protection product. If the shutter has problems, it will directly affect the fire resistance limit index of the rolling shutter. 2. The guide rail is deformed and the curtain board is stuck or falls unevenly. The fireproof rolling shutter door generally moves along the guide rail. If the guide rail is twisted or broken, the rolling shutter door will not be able to move to the specified position, which will not achieve the effect of fire separation. 3. On the roller shutter, the lower limit fails or the limit line is wrongly connected. Steel fireproof window Price This often happens on the fire roller shutter of the atrium. Because the fire roller shutter of the atrium is sometimes installed outside the walkway of the upper floor, there is no floor under the roller shutter to close it, and a large gap is leaked, so the fire separation of the upper and lower floors cannot be reached.