Maintenance and cultivation of fireproof rolling shutter door
All fire rolling shutters shall be inspected and tested once a week, and the test contents include: fire rolling shutters escape function test. After the fire roller shutter is in the linkage state and drops to the bottom, press any manual button on both sides of the fire roller shutter, and the fire roller shutter shall be able to rise to the limit position (or drop to the bottom again after a delay). The lifting, lowering and stopping test of the manual buttons on both sides of the fire shutter. The fire rolling shutter shall be able to operate according to the instructions, and the operation shall be stable without blocking, not to mention uneven running speed of the shutter, stacking of the shutter or derailment. Test of manual emergency device. The manual zipper is used to lift the fire shutter, and the manual quick release device is used to lower the fire shutter. The fire shutter shall be able to run smoothly. Simulate the fire signal for linkage test. It is required that the fire shutter should be able to descend according to the normal procedure, and the contents and parts displayed in the fire control room should be consistent with the actual situation. Check whether the sealing of fire shutter is intact and damaged. The inspection above Henan fire rolling shutter door shall be carefully recorded, and the problems found shall be solved in a timely manner without leaving hidden dangers. Check whether the appearance of the fire shutter is intact and whether the curtain surface is damaged.
The fire shutter door leaf cannot move: sensor failure is the major cause of the fire shutter door leaf cannot move. When such a situation occurs, be sure to check whether the sensor signal light is normal. If it is not the fault of the sensor, it may be that the wire connector is loose, the belt falls off, the controller is burned, the foreign matter is stuck, the voltage is abnormal, and so on. Pay attention to check and eliminate them one by one. The door leaf of the fire rolling shutter jumps when opening and closing: the reason for this fault is very simple. If the track of the fire rolling shutter is jammed by foreign matters, it is necessary to check the tracks on both sides of the door leaf, remove the foreign matters, and the fault can be solved. The opening and closing speed of the fire shutter door leaf is too slow: customers often hear this situation. It may be that the speed adjustment of the national controller is too slow, or the belt is too loose, resulting in friction between the fire shutter door leaf and the guide rail. When handling, check these two parts. If the speed is too slow, adjust them faster. If the belt is too loose, tighten it in time.
Maintenance of Henan fireproof rolling shutter door: the mechanical mechanism of the fireproof rolling shutter should be maintained every half a year, including oil injection, lubrication, etc., and check the wear degree of the mechanical mechanism and whether there is deviation; The commonly used safety tubes and contactors in the electrical part should be reserved enough to facilitate timely replacement; The insulation aging degree of the conductor shall be checked every half a year to measure whether the insulation resistance meets the requirements.